|
POWER GENERATION WITH PLASMA ARC TECHNOLOGY (PAT)
The
basis for this brief is to show the correlation between the Plasma Arc Technology (PAT) and Electrical Power Generation, which
are now possible when combined with the Air Vortex Pump (AVP) Continuous Feed System.
At present there are many different
ways of generating Electrical Power for Commercial Use. There are Hydroelectric Power Plants, Nuclear Power Plants, Steam
and Gas Turbine Power Plants, Diesel Engine Power Plants, and even Solar and Wind Power Plants. Each of these systems has
advantages based on location, power sources and cost of operation, and each has disadvantages for the same reasons but all
require continuous and Costly Fuel or Energy Inputs.
The most commonly utilized systems all burn Hydrocarbon Fuels
to get Diesel, Steam, or Turbine Power to run the Generators. Unfortunately, when compared to the Plasma Arc Technology (PAT)
these are very inefficient and Air Polluting Systems for generating Electricity.
We now have a Paradigm Shift in the
production of Fuel Energy to Power Electrical Generators. It is called Plasma Arc Technology (PAT), and it must utilize the
Air Vortex Pump (AVP) Continuous Feed Technology.
What is Plasma Arc Technology (PAT)?
Plasma Torches
have been in use for a long time as either Carbon Arc or Gaseous Plasma configurations. These High Temperature Systems are
used for Steel Production, Radioactive Waste Disposal, and other Industries that require Pollution Free, High Temperature
Equipment.
Advanced Technology Research - ATR, in combination with other Major U.S. Equipment Suppliers, is introducing
a Paradigm Shift with the Plasma Ion Bubble. This Stable Bubble represents a New Direction when combined with the Continuous
Flow of Materials into the Plasma Ion Field. The Material will be processed in this "Flow-Through to the Plasma Ion Bubble"
via the Air Vortex Pump (AVP).
The AVP Continuous Feed Development is the Major Breakthrough. Instead of the Normal
'12 Hour per Batch' System currently in use, the PAT Continuous Feed Furnace can process 22 Times the Single Hourly Rate of
the existing Process Technology each day.
How do we explain the Optimization of Power Production from PAT?
We
start with the explanation of Energy derived from Coal. When Coal is burned in a Power Plant, the Heat Output may often be
11,000 BTUs per lb. There is also substantial Pollution, which must be addressed through Scrubber Systems, which often account
for up to 40% of the Power Plant Capitalization Cost. In Third World countries this Pollution may be released into the Atmosphere,
or is just released into the Atmosphere – not the ideal solution. There is also a great deal of Ash and other Waste Material
to be addressed for disposal.
When the Coal is introduced to the Plasma Ion Bubble, a Phase Change occurs and the
Coal Hydrocarbons are reconstituted as Pure Methane, and are referred to as a 'Hot Gas'. This 1 lb of Coal now is equivalent
to approximately 44,000 BTUs of pure Methane. The equivalent of 11,000 BTUs is required to power the Plasma Ion Bubble therefore
leaving a Net Surplus of 33,000 BTUs of available Fuel Energy as 'Hot Gas' to drive the Turbines of an Electrical Power Plant.
This is 3 Times the Net Value obtained from burning Coal directly.
The by-product of the burning of Methane (CH4)
is Carbon Dioxide (CO2) and Water Vapor (H20). The Heavy Residues have been consumed in the process and are not released
as Pollutants but are reduced to approximately 4 lb of Inert Glass Residue for each ton of Feed Material. The Energy Release
from Hydrocarbon Materials (Coal or even Materials such as Municipal Solid Waste (MSW)) is over 99.99% with almost Zero Residues.
This means that all Pollution Standards will be achieved and surpassed.
What about Heavy Oils and other Hydrocarbon
Based Products – Bunker C etc.?
The same Power Production Ratios apply to other Hydrocarbon Based Products such as
Bunker Fuels. The PAT Process will convert the Hydrocarbon to Methane with substantially the same ratio increase of the BTU
Output. Many Tar Sands can also be processed to produce 1.2 bbl per ton of Crude Oil, which may be converted to Methane for
Hot Gas Turbine Fuel.
Garbage?
Standard Garbage (Municipal Solid Waste (MSW)) going to Landfills today
can be converted to Energy through the same PAT Process.
When Garbage processed with the AVP into the Continuous Flow
PAT Burner is converted to Methane, the rate is 4,400 BTUs per lb (8.8 Million BTUs per ton) of Garbage. 4 lb of Inert Glass
Residue is produced for every ton of Garbage processed.
Garbage introduced into the PAT Burner at the rate of 100
tons per hour will produce over 1 Megawatt (MW) of Generating Capacity. 4,000 tons per day will provide enough Energy for
40 Megawatts (MW) of Cogen Capacity.
In order to have an understanding of the amounts of Garbage produced by a City,
Mexico City produces 6,000 tons of Garbage per day or 60 MW of Cogen Potential. San Juan, Costa Rica produces 4,000 tons
per day or the equivalent of 40 MW of Cogen Potential.
It was recently announced that Toronto cancelled a $1 Billion
deal to ship "Millions" of tons of Garbage to the Adams Mines in northern Ontario for burial. The Garbage that they want
to throw away would provide enough Electrical Energy to Power the City of Toronto and thus automatically solve the Pollution
problem. They estimated that they would have a convoy of 1,000 trucks per day going to the Mine if the Railway deal folded,
as it has.
Costs?
The Costs of a Garbage Processing Facility will of course depend of the amount Garbage
you want it to be capable of handling.
The Costs for an Electrical Power Plant depend on whether there's an existing
one or not. If the Power Plant does not already exist, the rule of thumb for Capitalization for a new Electrical Power Plant
is about $1 Million per Megawatt (MW) of Power Production. However, the PAT Burner and AVP System could be located adjacent
to an existing Power Plant and replace all Virgin Hydrocarbon Fuels with the Methane resulting from PAT Garbage and/or Coal
Conversion. By eliminating the most costly elements of Air Quality Management, up to 40% of the above $1 Million per MW Cost
may be reduced leaving the Power Plant Capitalization Cost at about $600,000 per MW.
HDR TECHNOLOGY
The technology
to mine the heat from the hot rock found almost everywhere at some depth beneath the surface of the earth was conceived and
developed at Los Alamos between the years of 1970 and 1996. Conceptually, hot dry rock (HDR) heat mining is quite simple.
As shown in the drawing (above, left) water is pumped into hot, crystalline rock via an injection well, becomes superheated
as it flows through open joints in the hot rock reservoir, and is returned through production wells. At the surface, the useful
heat is extracted by conventional processes, and the same water is recirculated to mine more heat.
The key element
in successful heat mining is the development of an engineered geothermal reservoir in a hot body, impermeable rock. The point
in a hot rock body at which an HDR reservoir is created is determined by the selection of the location on the surface from
which the injection well is drilled and the depth within the wellbore at which the water is injected into the hot rock, while
the overall size of the reservoir is a direct function of the total amount of water pumped into the rock during its development.
Although these parameters can be engineered, the shape, orientation, and internal structure of the reservoir, are entirely
functions of the local geologic conditions and are, at present, beyond human control. For this reason, it is important to
understand the local geology before attempting to develop an HDR reservoir.
As an HDR reservoir is being formed, rock
blocks are moved very slightly by the injected water. These small movements give rise to low frequency stress waves similar
to, but much smaller than, those caused by earthquakes. Microseismic technology has been developed to identify these signals
and locate their points of origin. The data from many such signals provide a picture of the size, shape, and orientation of
the reservoir. With this information in hand, production wells can be drilled into the reservoir to most efficiently tap the
superheated water that has been injected.
An HDR system is operated by circulating water through the engineered reservoirs
at a pressure somewhat less than that used during its creation. Under these conditions the overall volume of the engineered
reservoir is relatively stable. In the closed-loop operation, the injection pump, working like the human heart, provides the
entire motive force for the circulation. Nothing except a small amount of waste heat is released to the environment.
GEOTHERMAL
ENERGY and HOT DRY ROCK (HDR) TECHNOLOGY One has to keep in mind that 99% of the earth mass is hotter than 1'000°C
and less than 0.1% is cooler than 100°C.
Over tens of thousands of hydrothermal manifestations on the earth surface,
such as boiling springs, hot fumaroles, mud pools and geysers, bear witness to hot fluid resources at depth.
Geothermal
resources have been used at least since Roman times for bathing and space heating. Nowadays, more than 60 countries world
wide are involved with direct uses of warm groundwater resources. Space heating, bathing, fish farming and greenhouses represent
the 77% of the applications, which represent in 2000 a total installed capacity of 16'200 MW thermal.
For the last
70 years, geothermal energy has also been converted into electricity. Today about 21 countries produce power with natural
geothermal steam rising from deep wells drilled into hot permeable aquifers. In 2000, the capacity of all the geothermal power
plants amounts to 8'000 MW electric.
The number of hydrothermal resources in highly permeable rock formations is limited.
However, there are huge land areas under which the rock temperature exceeds 200°C at depths less than 5 km. But, in general
the permeability of these formations is low, so that engineering and new technology will be necessary to generate energy production
economically. This is Hot Dry Rock (HDR) technology.
The principle of HDR technology is to circulate a fluid between
an injection well and a production well, along pathways formed by fractures in hot rocks. A deep heat exchanger is then created,
and the fluid transfers heat to the surface, where it can be converted to electricity. This process is contained into a closed-loop
and no gas or fluid escapes in the atmosphere. The hot fluid produced under pressure at the wellhead flows through a heat
exchanger, vaporizing a secondary low-boiling working fluid (Organic Rankine Cycle). This fluid, usually isobutane or ammonia,
is then passed through a turbine driving an electric generator.
Since the 1970's, a number of research programmes have
worked towards developing Hot Dry Rock (HDR) technology, first in the USA and the United Kingdom, then also in Germany, France,
Japan and Sweden. Recent projects have started in Australia and in Switzerland.
The terminology "Hot Dry Rock" has
evolved since formation fluids have been frequently found from deep boreholes drilled in crystalline rocks. Indeed, between
fully hydrothermal reservoirs and totally impermeable hot rocks, there is a complete series of low- to medium-permeability
rocks which cannot be exploited for geothermal energy production without specific engineering enhancements.
Names like
Hot Wet Rock (HWR) or Engineered Geothermal Systems can be found in the literature. The Swiss project is called Deep Heat
Mining (DHM) and recently the US Department of Energy renamed its new Hot Dry Rock programme into Enhanced Geothermal Systems
(EGS).
Several arguments give clear indications that time has arrived for commercialization of Enhanced Geothermal
Systems (EGS) energy production. New drilling techniques indeed are now available for deep and direction-controlled boreholes,
and programmes to reduce drilling costs by a significant amount are in progress. Moreover, environmental constraints lead
some countries to look for indigenous and clean energy resources. Finally, the cost-analysis of geothermal electricity produced
by EGS systems show decreasing trends for the price of the kilowatt per hour.
DEEP HEAT MINING
Power and
heat generation from deep enhanced geothermal systems: a new energy project in Switzerland.
Geothermal energy is the
only renewable source of energy which can be tapped round the year and the day with no need of storage facilities.
The
project was initiated and is partly financed by the Federal office of energy (OFEN) since 1996. Private and public institutions
support the activities of the project.
After the selection of a first adequate site in the city of Basel and the drilling
of the necessary boreholes, the objective is to create a deep fractured reservoir and to build a pilot plant delivering electricity
and heat.
The modular concept of a Deep Heat Mining pilot plant is composed of one injection well and one production
well. The cold water is pumped down and circulates through the fractured reservoir. This natural heat exchanger delivers hot
and pressurized water to the production wells. The energy is converted into power by means of a turbine-generator unit. The
excess heat is used for space heating. The cooled water is then reinjected at depth. This closed-loop system provides CO2-free
energy.
THE ADVANTAGES OF DEEP HEAT MINING THECNOLOGY A Deep Heat Mining plant can operate economically Calculation
based on present time investment costs show that the proposed pilot plant is economically justifiable with a continuous electrical
power production rate of 3 MWe and a maximum heat production rate of 20 MWth. Provided that these target parameters can be
met, even the pilot plant can achieve an economic break-even balance. If, as foreseen, the reservoir and the generating plant
are developed further, truly profitable operation will be possible.
A Deep Heat Mining plant offers ecological
advantages The exploitation of these deep-seated energy sources permits the production of electrical and thermal power
without waste products. The land requirements are particularly small and less than those which are characteristic of most
other alternative energy systems. The resulting reductions in CO2 emissions and fossil fuel usage as well as the increased
use of local resources will help in the fulfilment of declared political aims and obligations.
This project
will produce a multidisciplinary know-how There is little experience in Switzerland of exploration, drilling and engineering
at depths greater than 2500 m. However, a transfer of knowledge enabling the integration of the most modern drilling technology
to specific Swiss-based tasks has already been initiated. In the field of plant construction, Swiss industry is second to
none, but expertise in the use of geothermal fluids for electrical power generation lies principally abroad. The Deep Heat
Mining project promises to develop valuable experience in the creation and operation of geothermal reservoirs and to provide
an impulse in the development of surface plant and of plant engineering. This project should also underline the potential
of Swiss engineers and scientists for undertaking pioneering tasks.
|
CIRCUIT BREAKER TESTING TECHNOLOGY
This article
will explore the technology of testing high current circuit breakers. It will touch upon various aspects of circuit protection,
protective devices, and need for testing, but will focus upon the practical aspects of generating and measuring the high currents
required in the testing of circuit breakers.
CIRCUIT PROTECTION Circuit protection has been a factor in electrical
systems since the beginning of the Electrical Age, and has matured over the years. Any system involving electricity has a
source of power, conductors, and a device which uses the power. If any element fails, damage could occur, and protective devices
may be used to limit its extent.
Of primary consideration is the maximum available power. Batteries and generators
have maximum short circuit currents which are limited by their voltage and internal impedance, and severe overheating, mechanical
stresses, and explosion may occur if excessive fault currents flow for more than a brief time.
The conductors carrying
power to its destination are rated for a certain amount of continuous current, based on ambient temperature, insulation material,
and type of conductor. Excessive currents cause a temperature rise over time that will eventually damage the insulation or
even cause the conductor to melt.
In a power distribution system, where several users of power are connected to a
main source, it is usually desirable that the failure of one section of the network should not disturb the operation of other
sections. If protective devices are chosen properly, or coordinated, this effect may be achieved.
PROTECTIVE DEVICES
A protective device monitors one or more factor affecting safe operation of an electrical system, and produces an appropriate
response in case of a fault condition. The factors include current, voltage, wattage, phase angle, frequency, temperature,
and pressure. The appropriate response may be a visual, audible, or electrical signal, or a physical action which actually
interrupts the current or otherwise eliminates the fault condition. Additionally, this response may be intentionally delayed
by some period of time, which is often inversely proportional to the magnitude of the fault.
Fuses such as these
provide inexpensive and reliable protection from catastrophic failures and extreme fault currents. The devices covered
by this article will be limited to those that monitor the amplitude of a current, and react by interrupting that current when
it exceeds a predetermined value. The time delay from sensing the overcurrent to the actual interruption is assumed to be
determined by the amount of overcurrent as well as other factors, such as ambient temperature and recent history of overcurrents.
The simplest device is the fuse or fusible link. This is basically a conductor which is designed to melt in a specified
period of time at a given current, thereby breaking the circuit. Fuses are inherently the most reliable and least expensive
protective device, because of their simplicity and immunity to environmental contamination. Fuses, however, are inconvenient
if the circuit is subject to frequent fault conditions, since they must be physically replaced after each operation. In order
to provide greater convenience and versatility, circuit breakers were developed, which could be reset after being tripped
by a fault condition, and could be used to disconnect the circuit manually. The simplest circuit breakers use the
principle of electromagnetic trip with no intentional time delay. The current through a coil generates a magnetic field which
exerts a force against a preset trip mechanism. When this force is large enough, the trip mechanism begins to operate, and
after a period of time, determined by the amount of force, inertia, and other mechanical factors, the contacts open. Since
many electrical devices exhibit a considerable inrush current upon turn-on, or may produce temporary surges of current during
normal operation, it is often necessary to provide a time delay. Circuit breakers that meet this requirement may use various
combinations of heating coils and mechanical devices such as dashpots, or may employ electronic circuitry. The electronic
type may have complex testing requirements, and will not be covered here.
A special type of time-delay circuit
breaker is the motor overload relay. This type of device is used most often for the protection of electrical motors driving
compressors, where a temporary locked rotor condition may occur. In this case, a thermal element trips the contacts after
a moderate period of overcurrent, waits for a time, then resets itself, again applying power to the motor.
Sometimes
there are other situations where fault conditions may be temporary, as in the case of lightning strokes or tree branches falling
briefly across a power line. In such cases, the protective device may be in a remote area, and it would be inconvenient to
require someone to reset it after such transient incidents. For this reason, devices known as reclosers were developed. When
a fault occurs, the recloser trips, waits for a short period of time, and then resets itself. If the fault remains, it will
cycle through a series of trips and recloses, during which the cause of the fault may be removed, or it eventually locks in
a tripped condition. The testing of reclosers is similar to that for circuit breakers, but will not be covered in this article.
The last type of protective device to be discussed is the protective relay. This device consists of a circuit which
monitors one or more factors affecting the electrical system, such as current, voltage, frequency, etc., and closes a circuit
which trips one or more remotely located trip devices. The testing of protective relays has some commonality with circuit
breaker testing, but will not be covered here.
THE NEED FOR TESTING
Almost all people have experienced the
effects of protective devices operating properly. When an overload or a short circuit occurs in the home, the usual result
is a blown fuse or a tripped circuit breaker. Fortunately, few have the misfortune to see the results of a defective device,
which may include burned wiring, fires, explosions, and electrical shock. It is often assumed that the fuses and circuit
breakers in the home or industry are infallible, and will operate safely when called upon to do so ten, twenty, or more years
after their installation. In the case of fuses, this may be a safe assumption, because a defective fuse usually blows too
quickly, causing premature opening of the circuit, and forcing replacement of the faulty component. Circuit breakers, however,
are mechanical devices, which are subject to deterioration due to wear, corrosion, and environmental contamination, any of
which could cause the device to remain closed during a fault condition. At the very least, the specified time delay may have
shifted so much that proper protection is no longer afforded to devices on the circuit, or improper coordination causes a
main circuit breaker or fuse to open in an inconvenient location.
TESTING METHODS The manufacturers of circuit
breakers must test their designs under actual operating conditions, which requires the application of fault currents at the
rated voltage. Under such conditions, a circuit breaker will be subject to extreme mechanical and electrical stresses. At
the maximum interrupting rating, it may actually be damaged or destroyed, but if the fault current is safely interrupted,
the circuit breaker passes the test.
Naturally, it is impractical and unnecessary to test circuit breakers at full
power in the field. It is generally accepted practice to apply fault currents to circuit breakers at low voltage, in order
to test their time delay and instantaneous operating characteristics. AC or DC high voltage insulation tests, as well as visual
inspection, normally suffice to determine if the breaker will function safely under actual fault conditions.
Some
very high current circuit breakers employ current transformers, sense circuitry, and a trip signal to a set of main contacts,
to perform the current interruption function. Although testing could be performed using the primary injection method, it may
be very difficult and impractical. Therefore, a method called secondary injection is used, in which a current representative
of the output of the CT's is applied to the sense circuitry, and the trip signal is monitored. Crude functional tests
are sometimes used in the field, but are not recommended. Soldering guns, which produce one or two volts at up to 200 Amperes,
are sometimes applied to small breakers to see if they trip. However, the current is extremely variable, and there is no way
to check the time/current characteristic. Another method is the application of DC current from an automotive storage battery,
but this can produce currents large enough to damage the breaker, and can be very dangerous; moreover, the results are inconclusive.
CURRENT GENERATION REQUIREMENTS In order to understand the requirements for generating current for the
testing of circuit breakers, it is useful to examine the actual operation of a breaker under low voltage test conditions.
When voltage is first applied to a device from a low impedance source, such as the output of a transformer, current will begin
to flow according to the applied voltage and the overall impedance of the breaker, its connections, and the internal impedance
of the test set. The current sensing apparatus will eventually operate a trip mechanism, causing the main contacts of the
circuit breaker to open.
Some current will continue to flow as the contacts open, depending on resistance, source
impedance, applied voltage, stored inductive energy, etc. For the purposes of low voltage testing, the duration of such additional
current flow is normally minimal, but in some cases the change in impedance of the protective device may change sufficiently
during operation so as to affect the amount of current flow, even to the point of inhibiting operation. This is not often
encountered in simpler devices such as circuit breakers, but is very commonly seen in oil reclosers.
For the purposes
of this discussion, the effects of using a low-voltage source for testing will be explored. Most test gear uses an arrangement
of step-down transformers to generate a voltage which can be varied to produce currents in the device under test ranging from
well under its nominal operating current to at least six times, and up to twenty times, this value. At any given test current,
the combined impedance of the test set and the device under test interacts with the selected output voltage to produce that
current. If any one of these factors vary, the test current will also vary.
The applied voltage may change due to
variations in line voltage, which may be caused by changes in load, fluctuations in generator voltage, and heat generated
variations in line resistance. Some of these effects are very slow and minimal in overall effect, while others may cause essentially
instantaneous changes in voltage, and the resultant current. Line voltage may also exhibit some distortion (cyclic variations
from true sinusoidal waveform), which may cause related distortion in the output current.
The test set impedance will
generally remain fairly constant for a given setting of output voltage, but may vary considerably for various combinations
of input voltage, input taps, output taps, and vernier settings. Heating effects often necessitate changes in these settings,
resulting in impedance changes. Other factors, such as transformer design, wiring size, conductor routing, and connector resistance,
will also produce greatly varying test set impedance for the same output current.
The impedance of the device itself
will also affect overall current, and has the greatest likelihood of causing large, measurable changes in current during its
operation. The operating coil of an interrupting device is largely inductive, and its impedance is directly related to its
magnetic field. This field will change when any movement occurs in nearby ferrous objects, particularly its operating mechanism.
Depending on its construction, this will cause various amounts of inductance change, which will have some effect on the test
current. If this effect is great enough, and device is not fully committed to trip at this point, operation could actually
be inhibited.
The industry has an EIL ORT-560 Recloser Test Set, with a typical recloser. The test set uses resistors
to regulate the output current. Some improvement may be made by increasing the impedance of the test current source enough
to swamp out the effects of impedance change in the device under test. This is already being done in the some recloser test
sets, because of the very large impedance changes of oil reclosers, which can be as great as 5 to 1. However, without an active
source which electronically regulates the current, practical limitations dictate that some variation in test current must
be tolerated. This fact indicates that the measurement technology must somehow compensate for unavoidable distortion, and
still produce meaningful test results that correspond to the manufacturer's published time/current curves.
PRACTICAL
CURRENT GENERATION The generation of high currents for practical testing of circuit breakers is basically fairly simple.
First, it is necessary to know the impedance of the circuit breakers to be tested, as well as the impedance of all connecting
cables and buswork, to determine the voltage required to produce the test currents. Typically, this is in the order of one
to 24 volts.
The 50,000 amp EIL BTS-500S was the top of the line for many years. It used a single E-I output
transformer and tapped input autotransformer. Many are still in use today. In order to minimize the power requirements,
it is best to have a range of output taps on a transformer, to match the circuit breaker impedance as closely as possible.
The power rating of the transformer should be chosen to provide just enough power for the expected range of circuit breakers
to be tested, at a duty cycle representative of actual test requirements. It should be noted that a typical transformer capable
of 1000 amperes continuous can produce 2000 amperes for ten minutes in a half-hour interval (33% duty cycle), and can produce
a maximum of 10,000 to 20,000 amperes peak current into a short circuit, for several tenths of a second, enough to trip a
circuit breaker instantaneously. Once a suitable output transformer rating is determined, the actual design of the transformer
must be addressed.
The simplest design, used in many older test sets, uses a single E-I core, with a primary
winding of 240 or 480 VAC. The secondary consists of heavy copper wire or buswork, with one common connection, and two or
three taps for several ranges of output current and voltage. The disadvantages of this design are (1) the necessity of providing
a continuously variable source from zero to maximum voltage at full current capacity, and (2) the inefficiency of having unused
windings when operating at the highest current, lowest voltage tap. The driving source for the transformer is either a large,
multi-deck variable autotransformer, or a multi-tap autotransformer with a boost transformer and vernier. The advantage of
the multi-tap autotransformer is the capability of choosing among a range of input voltages.
Later designs, for larger
test sets, employ an array of several E-I cores, with two identical series output windings, which could be connected in series
or parallel for more efficient selection of output voltage/current rating. In some designs, one of the cores is made about
half the size of the others, so that a buck/boost configuration with a smaller vernier can be used. Overall weight and size
can be reduced substantially, since the primaries of the main elements are either shorted or connected directly to the input
supply voltage. A disadvantage of this design is that only one input voltage may be used. Multi-tapped primaries and series/parallel
connection of the vernier autotransformer could allow other voltages, but would be cumbersome to change in the field. The
EIL BTS-1000 used a multi-stage output transformer with series/parallel connections. It could produce over 100,000 amperes
into a short circuit, and was capable of testing the largest circuit breakers in general use.
A new variation
on this design is now being developed, using an arrangement of toroidal transformer cores and buswork. The well-known advantages
of toroids include greater efficiency, smaller size, lighter weight, and less acoustic and electrical noise. The configuration
under development also allows selection of three output arrangements, for better matching of impedance to the device under
test. A further advantage is modular construction, which permits flexible design and lower cost.
Another factor involved
in generating test currents is distortion of the current waveform. Since circuit breakers are largely inductive, an applied
voltage starting at a zero crossing will generate a high current transient, known as DC offset. This cannot be controlled
with contactors, but newer test set designs use SCRs, which can be gated to turn on at or near the voltage peak, resulting
in less DC offset and more repeatable readings.
(CONTINUED TOP RIGHT)
|
(CONTINUED FROM BOTTOM)
CURRENT SENSING TECHNOLOGY
Circuit breaker testing requires the measurement of currents from less than one ampere to about 100,000 amperes. There
are very few devices which can measure such a wide range of current to the required accuracy, which is in the order of 1%.
The most accurate current measurement device is probably the shunt, which is a precision resistor calibrated using
DC, to accuracies of 0.1% or better. AC accuracy at line frequencies is likely to be nearly as good, but inductance may cause
inaccuracies at higher frequencies. Shunts are readily available up to 10,000 amperes, and may be overloaded to ten or more
times their rating for short periods of time as applicable to breaker testing. One limitation of the shunt is its low output
voltage. A 10,000 ampere shunt will produce 100 millivolts at its rated current, but only one millivolt at 100 amperes. This
means that a 1% error at 100 amperes represents only 10 microvolts, which may be very small in proportion to the several volts
of common mode voltage, and hundreds of volts and thousands of amperes that are generated in the near vicinity of the measurement
equipment. Another drawback to the shunt is its large power requirement, or burden. The 10,000 ampere shunt requires 1000
watts at its rated current, which is tolerable, but at 20,000 amperes this grows to 4000 watts, and at 100,000 amperes, 100,000
watts is consumed. Shunts are very useful for calibration purposes, but have limited use in practical AC high current test
sets.
The traditional way to measure AC current at line frequencies is the iron core toroidal current transformer,
or donut CT. This device has isolation, low burden, low cost, high output, and good accuracy. Its limitations are its limited
useful range, and inability to measure DC components of the current waveform. Also, it is subject to saturation at high currents,
with resultant waveform distortion, and non-linearity at lower currents due to required magnetization currents. A multi-tapped
primary could be used for various current ranges, but this is unwieldy for a practical high current test set.
A popular
alternative to iron-core CT's is the air-core CT, which may be configured as a toroid, a two-pronged fork, or other arrangement.
A very simple CT of this type is an air-core inductor placed on or near the conductor of the current to be measured. The output
of an air-core CT is a voltage, which is proportional to the differential (rate of change) of the current. This is relatively
easily converted to read the actual current by performing an integration, which may be done with a resistor and a capacitor.
A great advantage to the air-core CT is its wide operating range, demonstrated to be at least 1000 to 1, combined with its
other qualities of low cost, low burden, wide frequency response, high isolation, and high output. Its chief limitation is
its sensitivity to stray magnetic fields, making its placement around the conductor and within the test set critical.
CURRENT
AND TIME MEASUREMENT REQUIREMENTS Most overcurrent protective devices operate on the true-RMS value of the applied current.
Electromagnetic breakers operate on the strength of a magnetic field, and are generally rated to work on DC as well as AC.
Highfrequency components are integrated out due to inductance and physical mass of the operating mechanism. Time-delay devices
usually use heaters or mechanical dashpots, which operate on the force-generating or heating effect of the current, which
is the definition of true-RMS. Thus, if the measuring circuitry can read the true-RMS value of the applied current waveform,
inaccuracies caused by distortion would be minimized.
Circuit breakers are designed to conform to published time-current
curves to an accuracy of about +/- 20%, which may apply to either current or time. In general, a circuit breaker is specified
not to trip at its rated current value, and must trip at a current of perhaps 150% of its rating. This means that a 20 Ampere
breaker may carry up to 29 Amperes forever, but must trip within several minutes at 30 Amperes. Time delay variations of 20%
or more are usually reasonable, and are generally specified from about 200% to as much as 1200% of rating. At higher currents,
breakers are expected to trip instantaneously, or with no intentional delay, which is typically no greater than 0.02 seconds,
or about one cycle.
CURRENT MEASUREMENT TECHNOLOGY The earliest high current measuring systems used iron vane
analog meters in conjunction with iron core CT's. Pulse current of short duration was measured by using a pointer preset mechanism,
which held the needle to the expected current. When the current pulse occurred, if the needle jumped, the preset amount of
current was assumed to have been reached. Current measurement was very approximate, and timing was performed using electromechanical
clocks, started at the time of initiation of output, and stopped when the breaker opened.
For reasons stated above,
air-core CT's soon replaced the iron core transformers. The output of the CT first goes through a voltage divider, which selects
an appropriate range. An integrator derives the true current signal, which is passed to a precision rectifier circuit. Its
output is the absolute value of the input, and the RMS value is not changed. The average of this signal is then obtained by
another integrator. Assuming a sinusoidal waveform, the RMS value may be calibrated as 1.1 times the average, but moderate
distortion may cause errors of up to 10%.
This type of measurement is generally adequate for moderately distorted
waveforms of sufficient duration to read a value visually, typically 1 second or longer. However, shorter duration pulses,
even one cycle (0.0167 sec) or somewhat less, are encountered with some regularity in breaker testing.
The "Duffers"
Memory Ammeter, used in many EIL circuit breaker test sets, incorporated peak reading circuitry, and used blanking to reduce
error from DC offset. It was soon replaced by the Accu-Amp, which used a true-RMS converter IC in conjunction with a fast-attack,
slow decay circuit.
One method of pulse measurement is a peak reading meter, which reads the peak absolute
value of the waveform. For pure sine waves, this is accurate, since the RMS value is simply 0.707 of the peak value. However,
distortion can produce errors of up to 30%. Another problem is that, depending on the phase angle of the initial portion of
the waveform, a "DC offset" is produced, due to circuit inductance, and could have a peak value as much as twice normal. It
is possible to "blank out" a number of measurement cycles, but this is impractical for very short pulses approaching one cycle.
An improved approach is a track-and-hold circuit, which may be adapted to the more accurate average-responding circuit.
In this case, the integrated output of a precision rectifier is gated to a storage element, typically a capacitor, while the
amplitude is above a preset value. A comparator is used to drive the gate while the actual signal remains above threshold.
The problem here is that an integrator with a ripple (or error) of less than 1% also has a rise time much greater than one
cycle, so either quick pulses are read as low, or random errors of greater than 1% are experienced.
One solution which
has worked to some degree of success is a "fast attack, slow-decay filter", which is a modified peak-hold circuit with an
intentional rate of decay. This eliminates some of the effects of DC offset at the beginning of a long pulse, but there are
still necessary trade-offs in response time and accuracy, even for sine wave signals. Practical accuracies of 5% or somewhat
better are obtainable for roughly sinusoidal signals of at least two or three cycles duration and minimal DC offset.
An
improvement in true-RMS measurement technology has been made with the introduction of true-RMS to DC converter IC's, which
perform a true-RMS conversion function using log and anti-log amplifiers, with an intermediate averaging function using a
capacitor. With the proper components, a settling time of about 20 mSec with 1% accuracy is possible, but this is still insufficient
for sub-cycle pulses. Combined with a fast-attack/slow-decay filter, accuracies approaching 2% on reasonably clean pulses
of 2 cycles or more can be obtained.
TIMING MEASUREMENT TECHNOLOGY The measurement of delay trip times of several
seconds on three-phase breakers is no problem. Early technology employed electromechanical clocks, which started when the
test current was applied to the breaker, and stopped when it tripped, as sensed by an auxiliary connection to an unused contact.
The typical error of about a tenth of a second is acceptable for trip times of several seconds. This method cannot be used,
however, for single pole breakers without unused or auxiliary contacts.
Such breakers required the use of a "current
latch" circuit, which served the dual purpose of providing a signal which could maintain the test current through the breaker
until it tripped, and operate the timer. A relatively simple circuit, consisting of a rectifier, filter, and threshold detector,
can be used for the latch requirement.
Instantaneous trip time measurements, in the order of several cycles, present
another challenge. Because of the turn-on delay of a contactor or SCR, and operating times of electromechanical relays, it
is necessary to use current measurement techniques for such fast timing measurements. If the current waveform is observed
on an oscilloscope, it is usually fairly easy to determine the start and stop points, even when there are discontinuities
and other noise in the waveform. However, designing a circuit to do this is more difficult. If a simple comparator, set at
5% of maximum value, is used on the rectified waveform, a series of pulses of varying duty cycle is formed. This signal can
be filtered and sampled by a second comparator, which should produce a step function which represents the time of the pulse.
Using such circuitry produces accuracies of 5 to 10 milliseconds on most pulses.
DIGITAL ELECTRONICS AND MICROPROCESSORS
With analog-to-digital conversion and microprocessor-based signal analysis, greater accuracy has been made possible.
Essentially, the signal is sampled by an A/D converter at several times the fundamental frequency, and the values stored in
memory. Various algorithms, implemented in software, read the current, and determine starting and stopping points. A true-RMS
calculation is performed on a selected part of the waveform, and the accuracy increases with the number of samples. Post-processing
can also be used to adjust for amplitude effects, and the actual waveform may be saved to a disk, viewed on a screen, or plotted.
The accuracy obtainable by using such methods should be in the order of 1% for amplitude, and 0.005 seconds for time. The
EIL PS-250 was one of the first breaker test sets to use a microprocessor, but it retained some of the original analog signal
preprocessing. Its major advantages were programmable auto-jog and current hold, and data storage, retrieval, and report printing.
Several new systems were developed in the late 80s and early 90s. The ubiquitous and ever more economical
IBM PC was used in several designs. A recloser test system was developed using a proprietary plug-in board for data acquisition
and control. It was incorporated in a rack-mounted computer that was an integral part of the test set. The problem of determining
the true-RMS value of the severely distorted waveforms was solved by performing a mathematical analysis of the stored A/D
samples. The software also interfaced to a database program for data storage, test result verification, and report generation.
An early attempt to use the PC for circuit breaker testing used a passive backplane system with an off-the-shelf data
processing board in conjunction with a proprietary interface to a keyboard and LCD display. This eliminated the awkward CRT
display and standard PC keyboard, but added considerable cost, and eliminated certain useful functions, such as waveform display
and custom reports. As the cost of portable PCs dropped, it soon became much more cost-efficient to use that platform, and
the proprietary interface was never put into production.
One of the first practical systems using a laptop computer
was developed in the early 90s, and was used in some new circuit breaker test sets as well as a retrofit system for older
units. A database program was also developed for this design. However, it was difficult to install the A/D board and proprietary
interface in the portable computer, and the interface was delicate and susceptible to electrical noise and mechanical damage.
Nevertheless, it is still in use in some breaker test sets currently in production.
As the convenience and versatility
of notebook style PCs became increasingly attractive and inexpensive, P S Technology pioneered the design of a parallel port
interface that could be used for data acquisition and control. Its first application was for recloser testing, in the form
of the ORTMASTER accessory, which was designed as a retrofit for existing test sets. It used an MSDOS program to display currents
and trip times, and interfaced to a database program for immediate verification of results to manufacturer's curves.
The
same basic hardware, with some modification and a different software program, was incorporated in a retrofit system for circuit
breaker testing. It is marketed by P S Technology as the STABMASTER.
Although the PC-based system has many advantages,
it was found to be too complex and fragile for many circuit breaker testing applications. In response to these concerns, P
S Technology developed the BTSMASTER, which is a self-contained measurement and control package. It uses a Z-180 based microprocessor
core, and is housed in a rugged rack-mountable enclosure that is mechanically and electrically compatible with the EIL Accu-Amp.
This feature makes it ideal for retrofit applications. The pushbutton controls and dual LED readouts are designed for simplicity
of operation and reliability, while the internal circuitry and firmware are optimized for accuracy.
The BTSMASTER,
P S Technology's latest breaker testing instrument, incorporates an A/D converter and microprocessor for true-RMS reading
of current, accurate reading of trip times, and a convenient programmable on time feature for auto-jog operation.
Future
developments in circuit breaker testing will probably focus on simplicity, reliability, accuracy, and affordability. This
will most likely be accomplished by a modular approach, with a simple, rugged main output unit, integral initiation and adjustment
controls, a self-contained monitor and control unit, and interface capability to separate computer systems for enhanced operation.
PRACTICAL TEST SYSTEMS Circuit breaker test sets should be designed according to requirements. For most purposes,
it is sufficient to test circuit breakers at one or two representative points on the time-current delay curve, to a timing
accuracy of +/- 0.1 seconds, and determine instantaneous trip current within about 5%. Very simple and inexpensive test sets
may be built with these specifications.
With microprocessor technology being inexpensive and versatile, it is now
possible to provide increased accuracy of testing, while also adding certain features to save time and reduce error. Test
set automation may include an auto-jog feature to determine instantaneous trip current, as well as automatic adjustment of
output current to a preset value for long-time testing. The addition of a computer can add additional benefits of automatic
set-up of the test set for various tests on standard breaker types, and interface to a database of test results for subsequent
analysis.
CONCLUSIONS The most important idea that should be derived from this article is the need to perform
regular testing on circuit breakers. We rely on their correct operation for protection from the extreme hazards that can be
produced by electricity, but only with proper testing can we have true confidence.
If it is agreed that regular testing
is necessary, it should also be apparent that reasonable accuracy must be guaranteed. This should be relatively easy to accomplish
by means of proper design and construction of specialized test equipment. Older test sets should be carefully tested for accuracy
and reliability, and if found to be deficient, they should be replaced or retrofitted with more modern measurement and control
systems.
Finally, it is important to analyze the overall picture, on the basis of cost. If circuit breakers are tested
regularly, the safety of the installation should be better, possibly resulting in lower insurance rates. If circuit breakers
can be tested more quickly with a new, computer-based test system, less time spent in testing will result in monetary savings.
Most important, if a comprehensive test program results in the saving of even one life, any effort or expenditure must be
considered worthwhile.
|